home *** CD-ROM | disk | FTP | other *** search
/ Spec Disk 1998 Spring 4.0 / Spec Disk 1998 Spring 4.0.iso / text / 15815met.txt < prev    next >
Text File  |  1998-06-10  |  11KB  |  295 lines

  1.                          SECTION 15815
  2.  
  3.                        FLEXIBLE DUCTWORK
  4. NOTE ** This section is based on flexible metal duct units
  5.         produced by:
  6. NOTE **
  7. NOTE **    METALFLEX Division, Professional Duct Systems,
  8.         Inc.
  9. NOTE **    6180 Boat Rock Boulevard, S. W.
  10. NOTE **    Atlanta, GA  30336
  11. NOTE **    Tel:  (888) MTL-FLEX (888-685-3539)
  12. NOTE **
  13. NOTE ** Products include UL-listed non-insulated and
  14.         insulated flexible aluminum duct, and non-listed
  15.         acoustical insulated duct.  METALFLEX UL-listed
  16.         duct is approved for use under numerous building
  17.         codes.
  18. NOTE **
  19. NOTE ** SECTION 15815 - FLEXIBLE DUCTWORK, Copyright 1997,
  20.         The Architect's Catalog, Inc.
  21.  
  22. PART 1  GENERAL
  23.  
  24. 1.1 SECTION INCLUDES
  25. NOTE ** Delete items below not required for project.
  26.  
  27.     A.  Non-Insulated Flexible Duct.
  28.  
  29.     B.  Insulated Flexible Duct.
  30.  
  31.     C.  Acoustical Insulated Flexible Duct.
  32.  
  33. 1.2 RELATED SECTIONS
  34. NOTE ** Delete any sections below not relevant to this
  35.         project; add others as required.
  36.  
  37.     A.  Section 15810 - Ducts.
  38.  
  39.     B.  Section 15822 - Sound Attenuators.
  40.  
  41. 1.3 REFERENCES
  42. NOTE ** Delete references from the list below that are not
  43.         actually required by the text of the edited
  44.         section.
  45.  
  46.     A.  ASTM C 518 - Standard Test Method for Steady-State Heat
  47.         Flux Measurements and Thermal Transmission Properties by
  48.         Means of the Heat Flow Apparatus.
  49.  
  50.     B.  ASTM E 84 - Standard Test Method for Surface Burning
  51.         Characteristics of Building Materials.
  52.  
  53.     C.  ASTM E 96 - Standard Test Methods for Water Vapor
  54.         Transmission of Materials.
  55.  
  56.     D.  NFPA 90A - Standard for Installation of Air Conditioning
  57.         and Ventilating Systems; National Fire Protection
  58.         Association.
  59.  
  60.     E.  NFPA 90B - Standard for Installation of Warm Air Heating
  61.         and Air Conditioning Systems; National Fire Protection
  62.         Association.
  63.  
  64.     F.  UL 181 - Standard for Factory Made Air Ducts and Air
  65.         Connectors; Underwriters Laboratory.
  66.  
  67. 1.4 SUBMITTALS
  68.  
  69.     A.  Submit under provisions of Section 01300.
  70.  
  71.     B.  Product Data:  Manufacturer's product literature for each
  72.         type unit.
  73. NOTE ** Delete paragraph below if building code not cited
  74.         in referenced Article.
  75.  
  76.     C.  Quality Assurance Submittals:  Certified test reports
  77.         from independent testing laboratory supporting compliance
  78.         of products to Building Code cited in QUALITY ASSURANCE
  79.         Article of this Section.
  80. NOTE ** Delete Article below if only acoustical insulated
  81.         duct units  specified.
  82.  
  83. 1.5 QUALITY ASSURANCE
  84.  
  85.     A.  Regulatory requirements:  UL compliance; affix UL Listing
  86.         Mark, with Class code, to each UL listed unit.
  87. NOTE ** Edit subparagraph below for applicable
  88.         jurisdiction; delete subparagraph if not
  89.         applicable.
  90.  
  91.         B.  Code compliance:  Units listed as complying with the
  92.             following:
  93.             1.  SBCC.
  94.             2.  ICBO.
  95.             3.  BOCA.
  96.             4.  HUD 515-2.1(b).
  97.             5.  City of Chicago, IL.
  98.             6.  New York, NY.
  99.             7.  San Francisco, CA.
  100.             8.  Dade County, FL Building Code.
  101.  
  102. PART 2  PRODUCTS
  103.  
  104. 2.1 MANUFACTURERS
  105.  
  106.     A.  Acceptable Manufacturer:  METALFLEX Division of
  107.         Professional Duct Systems, Inc., 6180 Boat Rock Blvd.,
  108.         S.W., Atlanta, GA  30336. ASD. Tel: (888) MTL-FLEX (888-
  109.         685-3539).
  110. NOTE ** Delete one of the two following paragraphs;
  111.         coordinate with Division 01 requirements.
  112.  
  113.     B.  Requests for substitutions will be considered in
  114.         accordance with provisions of Section 01600.
  115.  
  116.     C.  Substitutions:  Not permitted.
  117.  
  118.     D.  Supply all products specified in this section from a
  119.         single manufacturer.
  120.  
  121. 2.2 NON-INSULATED FLEXIBLE AIR DUCT
  122.  
  123.     A.  Acceptable Product:  METALFLEX V-100-UL.
  124. NOTE ** Select product V-100-UL for compressed duct; select
  125.         product V-100-S-UL for non-compressed duct.
  126.  
  127.     B.  Acceptable Product:  METALFLEX V-100-S-UL.
  128.  
  129.     C.  Materials:  Aluminum, formed into corrugated circular
  130.         duct in eight foot length with watertight seams and
  131.         continuous lock seam connection at each end.
  132.  
  133.     D.  Characteristics:
  134.         1.  Meet requirements of UL 181.
  135.         2.  Listed Class 0 Air Duct in accordance with NFPA 90A
  136.             and NFPA 90B.
  137.         3.  Fire Hazard Classification in accordance with ASTM E
  138.             84:
  139.             a.  Flame Spread:  Not exceeding 0.
  140.             b.  Smoke Developed:  Not exceeding 0.
  141.         4.  Maximum velocity air handling capability:  5000 feet
  142.             per minute.
  143.         5.  Maximum operating pressure, positive and negative:
  144.             a.  Duct diameter 3 inches to 10 inches:  Plus or
  145.                 minus 12 inches WG.
  146.             b.  Duct diameter 12 inches to 24 inches:  Plus or
  147.                 minus 8 inches WG.
  148.             c.  Operating temperature range:  Minus 100 degrees F
  149.                 to plus 430 degrees F.
  150. NOTE ** Retain sentence below if specifying product V-100-
  151.         UL.
  152.  
  153.         6.  Ship duct lengths compressed to 2 feet, 8 inch
  154.             length.
  155.  
  156.     E.  Accessories:  Furnish each length with universal
  157.         male/female connector at each end.
  158. NOTE ** Paragraph above specifies standard accessories for
  159.         product V-100-UL (compressed duct); paragraph below
  160.         specifies standard accessories for product V-100-S-
  161.         UL (non-compressed duct).
  162.  
  163.     F.  Accessories:  Furnish each length with male/female
  164.         connector one end.
  165.  
  166. 2.3 INSULATED FLEXIBLE AIR DUCT
  167. NOTE ** The V-200 product line has gray polyethylene vapor
  168.         barrier.  Select product V-200-UL for compressed
  169.         duct; select product V-200-S-UL for non-compressed
  170.         duct.
  171.  
  172.     A.  Acceptable Product:  METALFLEX V-200-UL.
  173.  
  174.     B.  Acceptable Product:  METALFLEX V-200-S-UL.
  175. NOTE ** The V-250 product line has metalized film vapor
  176.         barrier having greater moisture resistance than the
  177.         V-200 product line.  Select product V-250-UL for
  178.         compressed duct; select product V-250-S-UL for non-
  179.         compressed duct.
  180.  
  181.     C.  Acceptable Product:  METALFLEX V-250-UL.
  182.  
  183.     D.  Acceptable Product:  METALFLEX V-250-S-UL.
  184.  
  185.     E.  Materials:
  186.         1.  Inner Duct Core:  Aluminum, formed into corrugated
  187.             circular duct in eight foot length with watertight
  188.             seams and continuous lock seam connection at each
  189.             end.
  190. NOTE ** Standard insulating layer thickness is 1-1/2
  191.         inches; edit below if higher 'R' value is required.
  192.  
  193.         2.  Insulating Layer:  Non-combustible, 1-1/2 inches
  194.             thickness.
  195. NOTE ** The V-200 product line has gray polyethylene vapor
  196.         barrier; the V-250 product line has metalized film
  197.         vapor barrier.
  198.  
  199.         3.  Vapor Barrier:  Polyethylene, gray color, having 0.10
  200.             Perm rating in accordance with ASTM E 96, Procedure
  201.             A.
  202.         4.  Vapor Barrier:  Metalized film, having 0.05 Perm
  203.             rating in accordance with ASTM E 96, Procedure A.
  204.  
  205.     F.  Characteristics:
  206.         1.  Meet requirements of UL 181.
  207.         2.  Listed Class 1 Air Duct in accordance with NFPA 90A
  208.             and NFPA 90B.
  209.         3.  Fire Hazard Classification in accordance with ASTM E
  210.             84:
  211.             a.  Flame Spread:  Not exceeding 25.
  212.             b.  Smoke Developed:  Not exceeding 50.
  213.         4.  Maximum velocity air handling capability:  5000 feet
  214.             per minute.
  215.         5.  Maximum operating pressure, positive and negative:
  216.             a.  Duct diameter 4 inches to 10 inches:  Plus or
  217.                 minus 12 inches WG.
  218.             b.  Duct diameter 12 inches to 20 inches:  Plus or
  219.                 minus 8 inches WG.
  220.         6.  Operating temperature range:  Minus 20 degrees F to
  221.             250 degrees F.
  222. NOTE ** Ratings specified below are standard; edit if
  223.         higher thermal  efficiency required.
  224.  
  225.         7.  Thermal efficiency:
  226.             a.  C-factor, calculated at 75 degrees F mean:
  227.                 0.173.
  228.             b.  R-Value, calculated by ADC FD72-R1 method:  5.79
  229.                 average.
  230.             c.  R-Value, calculated by ASTM C 518 method:  4.2
  231.                 average.
  232. NOTE ** Retain sentence below if specifying product V-200-
  233.         UL or V-250-UL.
  234.  
  235.         8.  Ship duct lengths compressed to 2 feet, 8 inch
  236.             length.
  237.  
  238.     G.  Accessories:  Furnish each length with universal
  239.         male/female connector at each end.
  240. NOTE ** Paragraph above specifies standard accessories for
  241.         products V-200-UL and V-250-UL (compressed duct);
  242.         paragraph below specifies standard accessories for
  243.         products V-200-S-UL and V-250-S-UL (non-compressed
  244.         duct).
  245.  
  246.     H.  Accessories:  Furnish each length with male/female
  247.         connector one end.
  248.  
  249. 2.4 ACOUSTICAL INSULATED FLEXIBLE AIR DUCT
  250. NOTE ** Product V-450-S-DB has metalized film vapor barrier
  251.         with high moisture resistance. The product is non-
  252.         compressed duct.
  253.  
  254.     A.  Acceptable Product:  METALFLEX V-450-S-DB.
  255.  
  256.     B.  Materials:
  257.         1.  Inner Duct Core:  Aluminum, formed into corrugated
  258.             circular duct in eight foot length with watertight
  259.             seams and continuous lock seam connection at each
  260.             end.
  261.         2.  Insulating Layer:  Non-combustible, 1-1/2 inches
  262.             thickness.
  263.         3.  Vapor Barrier:  Metalized film, having 0.05 Perm
  264.             rating in accordance with ASTM E 96, Procedure A.
  265.  
  266.     C.  Characteristics:
  267.         1.  Maximum velocity air handling capability:  2500 feet
  268.             per minute.
  269.         2.  Maximum operating pressure, positive and negative,
  270.             for duct diameter 4 inches to 20 inches:  Plus or
  271.             minus 2 inches WG.
  272.         3.  Operating temperature range:  Minus 20 degrees F to
  273.             plus 250 degrees F.
  274.         4.  Thermal efficiency:
  275.             a.  C-factor, calculated at 75 degrees F mean:
  276.                 0.173.
  277.             b.  R-Value, calculated by ADC FD72-R1 method:  5.79
  278.                 average.
  279.             c.  R-Value, calculated by ASTM C 518 method:  4.2
  280.                 average.
  281.  
  282.     D.  Accessories:  Furnish each length with male/female
  283.         connector one end.
  284.  
  285. PART 3  EXECUTION
  286.  
  287. 3.1 INSTALLATION
  288. NOTE ** Verify specification section reference below.  Edit
  289.         if required.
  290.  
  291.     A.  Install flexible ductwork in accordance with provisions
  292.         of Section 15810 - Ducts.
  293.  
  294.                          END OF SECTION
  295.